DPM09 Digital Panel Meter

 

Measurement Displays: Features & Technical Parameters:

DPM09 is a multimeter which measures and displays:

- 3 phase currents (IL1, IL2, IL3).

- AC RMS values of 6 different voltages

  (VL1-N, VL2-N, VL3-N, VL1-L2, VL2-L3, VL3-L1)

- Frequency

- Over voltage (>120% of nominal V)/under

  voltage alarm (<80% of nominal V).

- Overload alarm/phase (>120% of CT rating).

 

Electrical Parameters:

System  : 3-phase, 4 wire unbalanced load.

Voltage: 380 / 220 VAC

Volt measurement range 85-270 VPH

Current: 5-amp from external current transformer.

Current transformer ratio: 5/5 to 2500/5

Current measurement range: 50 mA – 6 A (i.e. from 1% to 120%   of full scale)

Operating frequency: 45-65 HZ

Power supply          : From the measured voltages – no need for 

  a separate power supply.

Power supply voltage: From 85-280 VAC (thanks to the well     designed switch mode power supply)

Sampling rate: 833k. Samples/sec. @ 50 Hz.

Display: 3X3.5 digits (7 - segment,14 mm height-   highly illuminated red display)

Power consumption: < 1 watts.

Mechanical Parameters:

Operating temperature:-5 °C : 55 °C

Humidity: < 75% RH non-condensing.

Degree of protection: IP 40 (front panel)

Dimensions: 96X96X71 mm.

Panel cut out: 90+1X 90+1 mm.

Weight: 320 gm.

Standards             :   IEC 61010-1

                                    IEC 62052 Class 2

 

 

 

 

Other Related Products :    

- DPM10   Digital Multimeter

- DPM11   Digital Multimeter

- DPM13   Digital Multimeter

- DPM Plus OV/UV  Protection Multimeter

- DPM Plus OL  Protection Multimeter

- Smart06-A power factot controller

- Smart12-A power factor controller

 

Download Technical Data

 

 

 

 

Site Map  | ÚÑÈÜÜì

(c)Copyright 2005, Sigma. All rights reserved.